  • MEGGER PAT410 Full Database Driven Portable Appliance Testers – 200 mA bond Test

    # PAT410

    • Vast on-board memory to keep you the job longer
    • Continuous operation, no need to stop and wait for the tester to cool down
    • Instant re-start as you move from room to room testing
    MEGGER
    • MEGGER
    • PAT410

    PAT410 perfect for those content to bond test solely at 200 mA, The smallest, lightest of the PAT400 series weighs only 2.7 kg.

    • Vast on-board memory to keep you the job longer
    • Continuous operation, no need to stop and wait for the tester to cool down
    • Instant re-start as you move from room to room testing
    • Soft keys to speed you through the testing process
    • Full PAT testing including RCD testing
    • Most productive tester in its class
    Electrical Supply Range
    PAT410, PAT420, PAT450 230 V ±10 @ 50/60 Hz.
    PAT420, PAT450 110 V ± 10% + 110 V ±10% @50Hz.
    Bond Test (10A and 25A) Not PAT410
    Open Circuit Voltage 9 V AC ±10% ± 0.1 V (supply: 230 V 50 Hz).
    Earth Bond Resistance Accuracy ±5% ± 3 digits (0 to 0.49 Ω)
    ±5% ±5 (0.5 to 0.99 Ω).
    Display Range 0 to 1.99 Ω.
    Continuity Test (200mA)
    Continuity Test Voltage 9 V AC ± 10% ± 0.1 V (supply: 230 V 50 Hz).
    Continuity Resistance Accuracy ±5% ± 3 digits (0 to 0.49 Ω)
    ±5% ± 5 digits (0.5 to 0.99 Ω).
    Continuity Resistance Resolution 10 mΩ (1 to 19.99 Ω).
    Display Range 0 to 19.99 Ω.
    Insulation Test (250V and 500V)
    Insulation Resistance Accuracy (230 V) ±2% ± 5 digits (0 to 19.9 MΩ)
    ±5% ± 10 digits (20 to 99.99 MΩ).
    Insulation Resistance Resolution 0.01 MΩ.
    Display Range 0 to 99.99 MΩ.
    Substitute Leakage Test
    Test Voltage and Frequency 40 V AC ±10% nominal mains frequency.
    Leakage Current Accuracy ±5% ± 5 digits.
    Leakage Current Resolution 0.01 mA.
    Display Range 0 to 19.99 mA.
    Differential Leakage Current
    Test Voltage Nominal mains 110/230 V AC.
    Test Frequency Nominal mains 50/60 Hz.
    Differential Leakage Current Accuracy ±5% ± 0.05 mA (1.0 mA to 9.99 mA)
    ±5% ± 0.1 mA (0.1 mA to 0.99 mA).
    Resolution 0.01 mA.
    Display/Measurement Range 0.10 mA to 19.99 mA.
    Touch Current Test
    Test Voltage and Frequency Nominal mains supply.
    Touch Current Accuracy ±5% ± 5 digits.
    Touch Current Resolution 0.01 mA.
    Display 0 to 10 mA.
    Operational Test
    Test Voltage and Frequency Nominal mains supply.
    VA Rating 230 V 3700 VA
    110 V 1800 VA.
    VA Accuracy ±5% ± 10 digits (0 to 99 VA)
    ±5% ± 50 digits (100 VA to 999 VA)
    ±5% ± 100 digits (1000 VA to 3700 VA).
    Resolution 1 VA (0 to 3700 VA).
    Display Range 0 to 3990 VA.
    Extension Lead Test
    Tests Performed Bond, insulation and polarity.
    Polarity Test Voltage 12 V.
    Polarity checks Lead ok
    Live neutral S/C
    Live neutral reversed
    Live/neutral O/C.
    Flash Test (PAT450 only)
    Flash Test Voltage 1500 V AC nominal for class 1
    3000 V AC nominal for class 2.
    Flash Test Current <3.5 mA short circuit @ 253 V primary supply voltage.
    Flash Test Breakdown Current Accuracy ±5% ±5 digits.
    Flash Test Breakdown Current Resolution 0.01 mA.
    Display Range 0 to 3.0 mA.
    Portable RCD Test
    Test Voltage and Frequency Nominal mains supply.
    Test Current Accuracy -8% to -2% (1/2 x I)
    +2 to +8% (1 x I, 5 x I).
    Trip Time Accuracy ±1% ± 5 digits.
    Trip Time Resolution 0.1 ms.
    Display Range 0 to 1999 ms (1/2 x I)
    0 to 300 ms (1 x I)
    0 to 40 ms (5 x I).
    Fuse Test
    Test Voltage 3.3 V.
    Warning Audible beep if fuse is OK.
    Environmental
    Operating Temperature -10 to 50°C.
    Storage Temperature -20 to 60°C.
    Humidity 90% RH @ -10 to 30°C
    75% RH @ +30 to 50°C.
    Maximum Altitude 2000m.
    Ingress Protection IP40.
    General
    Weight 4.4 kg.
    Dimensions 180 (H) x 255 (W) x 320 mm (L).
    Safety IEC 61010-1: CAT II 300 V.
    EMC IEC 61326-1: 2006
    IEC 61326-2-2: 2005.
    Megger PAT410 warranty One-year.