Add products to your Toolbox to save it for requesting a quote while you keep browsing for other products to complete your list.
# PAT410
PAT410 perfect for those content to bond test solely at 200 mA, The smallest, lightest of the PAT400 series weighs only 2.7 kg.
Electrical Supply Range | |
---|---|
PAT410, PAT420, PAT450 | 230 V ±10 @ 50/60 Hz. |
PAT420, PAT450 | 110 V ± 10% + 110 V ±10% @50Hz. |
Bond Test (10A and 25A) Not PAT410 | |
Open Circuit Voltage | 9 V AC ±10% ± 0.1 V (supply: 230 V 50 Hz). |
Earth Bond Resistance Accuracy | ±5% ± 3 digits (0 to 0.49 Ω) ±5% ±5 (0.5 to 0.99 Ω). |
Display Range | 0 to 1.99 Ω. |
Continuity Test (200mA) | |
Continuity Test Voltage | 9 V AC ± 10% ± 0.1 V (supply: 230 V 50 Hz). |
Continuity Resistance Accuracy | ±5% ± 3 digits (0 to 0.49 Ω) ±5% ± 5 digits (0.5 to 0.99 Ω). |
Continuity Resistance Resolution | 10 mΩ (1 to 19.99 Ω). |
Display Range | 0 to 19.99 Ω. |
Insulation Test (250V and 500V) | |
Insulation Resistance Accuracy (230 V) | ±2% ± 5 digits (0 to 19.9 MΩ) ±5% ± 10 digits (20 to 99.99 MΩ). |
Insulation Resistance Resolution | 0.01 MΩ. |
Display Range | 0 to 99.99 MΩ. |
Substitute Leakage Test | |
Test Voltage and Frequency | 40 V AC ±10% nominal mains frequency. |
Leakage Current Accuracy | ±5% ± 5 digits. |
Leakage Current Resolution | 0.01 mA. |
Display Range | 0 to 19.99 mA. |
Differential Leakage Current | |
Test Voltage | Nominal mains 110/230 V AC. |
Test Frequency | Nominal mains 50/60 Hz. |
Differential Leakage Current Accuracy | ±5% ± 0.05 mA (1.0 mA to 9.99 mA) ±5% ± 0.1 mA (0.1 mA to 0.99 mA). |
Resolution | 0.01 mA. |
Display/Measurement Range | 0.10 mA to 19.99 mA. |
Touch Current Test | |
Test Voltage and Frequency | Nominal mains supply. |
Touch Current Accuracy | ±5% ± 5 digits. |
Touch Current Resolution | 0.01 mA. |
Display | 0 to 10 mA. |
Operational Test | |
Test Voltage and Frequency | Nominal mains supply. |
VA Rating | 230 V 3700 VA 110 V 1800 VA. |
VA Accuracy | ±5% ± 10 digits (0 to 99 VA) ±5% ± 50 digits (100 VA to 999 VA) ±5% ± 100 digits (1000 VA to 3700 VA). |
Resolution | 1 VA (0 to 3700 VA). |
Display Range | 0 to 3990 VA. |
Extension Lead Test | |
Tests Performed | Bond, insulation and polarity. |
Polarity Test Voltage | 12 V. |
Polarity checks | Lead ok Live neutral S/C Live neutral reversed Live/neutral O/C. |
Flash Test (PAT450 only) | |
Flash Test Voltage | 1500 V AC nominal for class 1 3000 V AC nominal for class 2. |
Flash Test Current | <3.5 mA short circuit @ 253 V primary supply voltage. |
Flash Test Breakdown Current Accuracy | ±5% ±5 digits. |
Flash Test Breakdown Current Resolution | 0.01 mA. |
Display Range | 0 to 3.0 mA. |
Portable RCD Test | |
Test Voltage and Frequency | Nominal mains supply. |
Test Current Accuracy | -8% to -2% (1/2 x I) +2 to +8% (1 x I, 5 x I). |
Trip Time Accuracy | ±1% ± 5 digits. |
Trip Time Resolution | 0.1 ms. |
Display Range | 0 to 1999 ms (1/2 x I) 0 to 300 ms (1 x I) 0 to 40 ms (5 x I). |
Fuse Test | |
Test Voltage | 3.3 V. |
Warning | Audible beep if fuse is OK. |
Environmental | |
Operating Temperature | -10 to 50°C. |
Storage Temperature | -20 to 60°C. |
Humidity | 90% RH @ -10 to 30°C 75% RH @ +30 to 50°C. |
Maximum Altitude | 2000m. |
Ingress Protection | IP40. |
General | |
Weight | 4.4 kg. |
Dimensions | 180 (H) x 255 (W) x 320 mm (L). |
Safety | IEC 61010-1: CAT II 300 V. |
EMC | IEC 61326-1: 2006 IEC 61326-2-2: 2005. |
Megger PAT410 warranty | One-year. |
Product selected: Model #