• Store Locator
  • Schedule a
    Demo
  • Add products to your Toolbox to save it for requesting a quote while you keep browsing for other products to complete your list.

    My
    Toolbox
  • MEGGER PAT150R Handheld Portable Appliance Testers with RCD – Rechargeable

    # PAT150R

    • Simple tick or cross, pass or fail indication plus measurement
    • Tough, rubber armoured with built-in front cover, hardened, scratch-proof display window
    • Includes 250 V insulation and leakage testing for safe IT testing and surge protected devices

    PAT150R is a rechargeable version of the PAT150.

    • Simple tick or cross, pass or fail indication plus measurement
    • Tough, rubber armoured with built-in front cover, hardened, scratch-proof display window
    • Includes 250 V insulation and leakage testing for safe IT testing and surge protected devices
    • Testing portable and fixed electrical equipment
    • 10 mA and 30 mA portable RCD lead testing (PAT150)
    • Adjustable PASS test limits (PAT150)
    • Substitute and mains powered leakage testing (PAT150)
    • Battery powered with rechargeable options
    SpecificationsMegger PAT120Megger PAT150
    Environmental Conditions
    Operating Ambient20°C20°C
    HumidityNominal humidityNominal humidity
    Continuity Testing
    Test VoltageCompliance voltage: +4V DC-0 / +10% (open circuit)Compliance voltage: +4V DC-0 / +10% (open circuit)
    Test CurrentBi-directional +200mA-0% + 50mA (into 2Ω load)Bi-directional +200mA-0% + 50mA (into 2Ω load)
    Continuity AccuracyResistance: ±5% ± 3 digits (0 to 19.99Ω)Resistance: ±5% ± 3 digits (0 to 19.99Ω)
    Resistance Resolution10mΩ10mΩ
    Display Range0.01 to 19.99Ω0.01 to 19.99Ω
    Continuity Test NullingUp to 9.99ΩUp to 9.99Ω
    Test DurationSelected during test automaticallyUser-selectable from 2 seconds to 20 seconds or selected during test to 180 seconds
    Insulation Test
    Insulation Procedure250V DC: -0% / +25% open circuit250V DC: -0% / +25% open circuit500V DC: -0% / +25% open circuit

    ≥ 500V 0% DC across 0.5MΩ load

    Short Circuit/Charge Current<2mA DC<2mA DC
    Insulation Accuracy±3% ± 10 digits (0 to 99.9MΩ)±3% ± 10 digits (0 to 99.9MΩ)
    Resolution0.01MΩ0.01MΩ
    Display Range0.10M to 99.99MΩ0.10M to 99.99MΩ
    Test DurationSelected during test automaticallyUser selectable from 2 seconds to 20 seconds or selected during test to 180 seconds
    Substitute Leakage Test
    Leakage CurrentAccuracy ±5% ± 3 digitsAccuracy ±5% ± 3 digits
    Test FrequencyNominal mains frequency 50HzNominal mains frequency 50Hz
    Test Voltage<50V AC<50V AC
    Resolution0.01mA0.01mA
    Display Range0.10 to 19.99mA0.10 to 19.99mA
    Test DurationUser-selectable from 2 secs to 5 secondsUser-selectable from 2 secs to 5 seconds
    Differential Leakage Test (PAT150 Only)
    Test VoltageNominal supply voltage 230V AC
    Test FrequencyNominal mains frequency 50Hz
    Test Accuracy±5% ±3d ± 3μA/A
    Resolution0.01mA
    Display Range0.10 to 19.99mA
    Test DurationUser-selectable from 2 seconds to 5 seconds
    Touch Current Test (PAT150 Only)
    Test VoltageNominal mains 230V AC
    Test FrequencyNominal mains 50Hz
    Test Accuracy±5% ± 3 digits
    Resolution0.01mA
    Display Range0.10 to 3.99mA
    Test DurationUser-selectable from 2 seconds to 5 seconds
    SELV Device Test (PAT150 Only)
    Test Voltage0 to 300V AC
    Measurement Accuracy±3% ± 3 digits
    Resolution0.1V AC
    Display Range0.1 to 300V AC
    Extension Lead Test
    Test Voltage5V5V
    PolarityLead OKLive/neutral shorted

    Live/neutral reversed

    Live/neutral open circuit

    Lead OKLive/neutral shorted

    Live/neutral reversed

    Live/neutral open circuit

    Portable RCD Test (PAT150 Only)
    Test VoltageNominal mains 230V
    Test Frequency50Hz
    Test Current Accuracy+2% to +8% (1 x I, 5 x I)
    Trip Time Accuracy±1% ± 1ms
    Trip Time Resolution0.01ms
    Display Range0 to 200ms (1 x I)0 to 40ms (5 x I)
    Mains Supply Test (PAT150 Only)
    Frequency Measurement Range50Hz
    Test Voltage40 to 300V AC
    Accuracy±3% ± 3 digits
    Resolution0.1V AC
    Display Range40 to 300V AC
    Circuit Test
    Test Voltage5V5V
    Test FrequencyNominal mains 50HzNominal mains 50Hz
    Test Current<100mA short circuit<100mA short circuit
    SafetyInstrument designed to IEC 61010-1: 2012Test leads designed to IEC 61010-031:2005

    300 volts to Earth Category II

    Mains fuse protection to 250V RMS AC

    Instrument designed to IEC 61010-1: 2012Test leads designed to IEC 61010-031:2005

    300 volts to Earth Category II

    Mains fuse protection to 250V RMS AC

    EMCDesigned to meet IEC 61326-1: 2006 and IEC 61326-2-2: 2005Designed to meet IEC 61326-1: 2006 and IEC 61326-2-2: 2005
    Environmental
    Operating Temperature0 to 40°C0 to 40°C
    Storage Temperature-20 to 60°C-20 to 60°C
    Humidity90% RH @ 10 to 30°C75% RH @ 30 to 40°C90% RH @ 10 to 30°C75% RH @ 30 to 40°C
    Max Altitude2000m to full safety spec2000m to full safety spec
    IP RatingIP40 (with front cover closed)IP40 (with front cover closed)
    Mechanical (Batteries)
    Battery Life3 days based on 120 tests/day using 2000mAh alkaline batteries3 days based on 120 tests/day using 2000mAh alkaline batteries
    Battery TypeSupply voltage12V DC (alkaline AA LR6)

    9.6V DC (NiMH AA LR6)

    Supply voltage12V DC (alkaline AA LR6)

    9.6V DC (NiMH AA LR6)

    Weight1150g1300g
    Dimensions203mm (L) x 148mm (W) x 78mm (H)203mm (L) x 148mm (W) x 78mm (H)

    Provide us your contact detailsone of our product experts will contact you to discuss your needs or schedule a demonstration at a time that suits

    Product selected: Model #







      *Demonstrations can only be scheduled within the UAE

      Sign up to stay in the know-how of our latest products, updates, special offers, and more.

      • Subscription Form