• Store Locator
  • Schedule a
    Demo
  • Add products to your Toolbox to save it for requesting a quote while you keep browsing for other products to complete your list.

    My
    Toolbox
  • Create a Requisition

    MEGGER MIT417/2 1 kV insulation and continuity testers

    # MIT417/2

    • Designed for electrical and industrial applications
    • Suitable for electrical installations, cable testing, motor testing, automotive applications, ESD, panel building, avionics and other maintenance
    • Feedback-controlled test voltages for insulation testing
    • Designed for electrical and industrial applications
    • Suitable for electrical installations, cable testing, motor testing, automotive applications, ESD, panel building, avionics and other maintenance
    • Feedback-controlled test voltages for insulation testing
    • Tests at 10V, 25V, 50V, 100V, 250V, or 500V (0% to +2%)
    • Continuity testing with continuous resistance range and test currents at 20mA and 200mA
    • True RMS voltage measurement up to 600V AC/DC
    • Polarisation index and dielectric absorption ratio
    • Weatherproof to IP54 standard
    • Shock-proof, over-moulded design
    • Clear, digital display with analogue arc
    • Live circuit detection for improved safety
    • Buzzer alarm for continuity and insulation testing

    Insulation

    Nominal test voltage

    • MIT415/2, 10 V, 25 V, 50 V, 100 V, 250 V, 500 V,
    • MIT417/2 10 V, 25 V, 50 V, 100 V, 250 V, 500 V, 1000 V

    Insulation accuracy

    • 50 Volts: 10 GΩ ± 2% ± 2 digits ± 4.0% per GΩ
    • 100 Volts: 20 GΩ ± 2% ± 2 digits ± 2.0% per GΩ
    • 250 Volts: 50 GΩ ± 2% ± 2 digits ± 0.8% per GΩ
    • 500 Volts: 100 GΩ ± 2% ± 2 digits ± 0.4% per GΩ
    • 1000 Volts: 200 GΩ ± 2% ± 2 digits ± 0.2% per GΩ

    Service Error: BS EN 61557-2 (2007)

    • 50V: ± 2.0% ± 2d, 100 kΩ – 900 kΩ ± 10.5%
    • 100V: ± 2.0% ± 2d, 100 kΩ – 900 kΩ ± 10.3%
    • 250V: ± 2.0% ± 2d, 100 kΩ – 900 kΩ ± 10.3%
    • 500V: ± 2.0% ± 2d, 100 kΩ – 900 kΩ ± 10.3%
    • 1000V: ± 2.0% ± 2d, 100 kΩ – 900 kΩ ± 11.5%
    • Display range analogue: 1 GΩ full scale
    • Resolution: 0.1 kΩ
    • Short circuit/charge current: 2 mA +0% -50% to EN 61557-2 (2007)
    • Open circuit voltage insulation: -0% +2% ± 2V
    • Test current: 1 mA at min. pass value of insulation to a maximum of 2 mA max.
    • Leakage: 10% ±3 digits
    • Voltage: 3% ±3 digits ±0.5% of rated voltage
    • Timer control: 60 second countdown timer
    • Note: Above specifications only apply when high quality silicone leads are being used.

    Continuity

    • Continuity measurement: 0.01 Ω to 999 kΩ (0 to 1000 kΩ on analogue scale)
    • Continuity accuracy: ± 3% ± 2 digits (0 to 100 Ω ) / ± 5% ±2 digitis (>500 kΩ- 1MΩ)
    • Service Error: BS EN 61557-4 (2007) – ± 2.0%, 0.1 Ω – 2 Ω ± 6.8%
    • Open circuit voltage: 5 V ± 1 V
    • Test current: 200 mA (–0 mA +20 mA) (0.01 Ω to 4 Ω)
    • Polarity: Single polarity (Default) / Dual polarity (configurable on setup).
    • Lead resistance: Null up to 9.00 Ω

    Voltage

    • Voltage range AC: 10 mV to 600 V TRMS sinusoidal (15 Hz to 400 Hz)
    • Voltage range DC: 0 to 600 V
    • Volt range accuracy AC: ±2% ±1 digit
    • Volt range accuracy DC: ±2% ±2 digit
    • Service Error: BS EN 61557-1 (2007) – ± 2.0% ± 2d, 0 V – 300 V AC/DC ± 5.1%
    • Waveform Unspecified range: 0 – 10 mV (15 to 400 Hz)
    • For non-sinusoidal waveforms additional specifications apply non-sinusoidal waveforms: ±3% ± 2 digits >100 mV to 600 V TRMS ±8% ± 2 digits 10 mV to 100 mV TRMS

    Frequency

    • Frequency measurement range: 15 Hz – 400 Hz
    • Frequency measurement accuracy: ±0.5% ± 1digit (100 Hz to 400 Hz unspecified)

    Power supply

    • Batteries: 6 x 1.5 V cells, type IEC LR6 (AA, MN1500, HP7, AM3 R6HP) Alkaline / 6 x 1.2 V NiMH rechargeable cells may be used
    • Battery life: 3000 insulation tests with duty cycle of 5 sec ON /55 sec OFF @ 1000 V into 1 MΩ
    • Dimensions: Instrument 228 mm x 108 mm x 63 mm (9.00 in x 4.25 in x 2.32 in)
    • Weight: 600 g (MIT400/2), (1.32 lb)
    • Weight (instrument and case): 1.75 kg (3.86 lb)
    • Fuse: Use only 1 x 500 mA (FF) 1000 V 32 x 6 mm ceramic fuse of high breaking capacity HBC 10 kA minimum. Glass fuses MUST NOT be fitted.
    • Safety protection: The instruments meet EN 61010-1 (1995) to 600 V phase to earth, Category IV. Refer to safety warnings supplied.
    • EMC: In accordance with IEC 61326 including amendment No.1
    • Temperature co-efficient: <0,1% per °C up to 1 GΩ; <0,1% per °C per GΩ above 1 GΩ

    Environmental

    • Operating temperature range and humidity: -10 to +55 °C; 90% RH at 40 °C max.
    • Storage temperature range: -25 to +70 °C
    • Calibration temperature: +20 °C
    • Maximum altitude: 2000 m
    • IP rating: IP 54

    Provide us your contact detailsone of our product experts will contact you to discuss your needs or schedule a demonstration at a time that suits

    Product selected: Model #







      *Demonstrations can only be scheduled within the UAE

      Sign up to stay in the know-how of our latest products, updates, special offers, and more.

      • Subscription Form