Insulation ranges |
Nominal Test Voltage | 1000 V, 500 V, 250 V (d.c.) |
Measuring Range |
All instruments | 10 k½ – 999 M½ on all ranges |
Short Circuit Current | 1.5 mA nominal |
Test Current on Load | 1 mA at min. pass values of insulation (as specified in BS7671, HD 384 and IEC 364) |
Accuracy (at 20° C) | ±3%, ±2 digits |
Continuity ranges |
Measuring Range | 0,01 ½ – 99,9 ½ (0 -50 ½ on analogue scale) |
Open Circuit Voltage | 5 V ±1 V |
Short Circuit Current | 200 – 215 mA |
Terminal Characteristics |
|
Accuracy (at 20° C) | ±3% ±2 digits |
Zero Offset Adjust | 0 – 9 ½ |
Continuity Buzzer | Adjustable 1 ½ to 20 ½
Response time <20 ms |
Resistance range |
(can be used for diode testing) |
Measuring Range | 10 ½ – 1 M½ |
Open Circuit Voltage | 5 V |
Short Circuit Current | 1.5 mA |
Accuracy (at 20° C) | ±5% ±2 digits up to 100 k½ |
Voltage range |
Measuring Range | 0 – 600 V a.c. (50/60 Hz) or d.c. |
Accuracy (at 20° C) | d.c. or a.c. (50/60 Hz) ±1%, ±2 digits |
Temperature coefficient | <0,1% per °C on all ranges. |
Default voltmeter |
(all modes except off) | >25 V a.c. or d.c. is applied display will operate as a voltmeter. |
Test inhibit | If more than 50 volts is detected, testing will be inhibited. |
AutoPower Down | Auto power down operates after 10 minutes if left in standby mode. |
Temperature and humidity |
Operating Range | -10°C to +60°C |
Operating Humidity | 93% R.H. at +40°C max.: |
Storage Range | -25°C to +70°C |
Test Result Storage (1000 results) |
Job Number | 255 locations |
Distribution Board no. | 99 locations |
Circuits | 99 locations |
Phases | P1, P2, P3 |
Last recorded result may be recalled to the display.
All data can be downloaded to a PC using Download Manager (supplied) or Megger Powersuite Professional of Windows software |
Communications | USB interface |
Environmental Protection | IP54 |
Fuses | Terminals 500 mA (F) 600 V, 32 x 6 mm Ceramic HBC 10 kA minimum. |
Display shows if fuse is ruptured. |
Safety | Meets the requirements of IEC61010-1 Cat III 600 V phase to earth. |
Automatic discharge | After an insulation test the item under test will be discharged automatically. Any voltage present will be indicated on the display so that the discharge can be monitored. |
Power supply |
Battery | 8 x 1,5 V cells IEC LR6 type(AA alkaline).
Rechargeable NiCd or NiMH cells may be used.
Battery condition is constantly shown on the display as a four-section bargraph. |
Battery Life | 5000 consecutive tests (5 seconds per test) on any test using 2Ah batteries. Weight |
All units | 980 gms |
Dimensions | All units: 203 x 148 x 78 mm (8 x 5.7 x 3.2 inches) |
E.M.C. | In accordance with IEC61326 including amendment No.1 |