Add products to your Toolbox to save it for requesting a quote while you keep browsing for other products to complete your list.
# 1748/30/EUS
Software Features:
Hardware Features:
Electrical Specifications | |
Power Supply | |
Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit |
100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7) | |
Power consumption | Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter) |
Efficiency | ≥ 68.2% (in accordance with energy efficiency regulations) |
Maximum no-load consumption | < 0.3 W only when powered using IEC 60320 input |
Mains power frequency | 50/60 Hz ±15% |
Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
On-battery runtime | Typically 4 hours |
Charging time | < 6 hours |
Data Acquisition | |
Resolution | 16-bit synchronous sampling |
Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency |
Input signal frequency | 50/60 Hz (42.5 to 69 Hz) |
Circuit types | 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies) |
Data storage | Internal flash memory (not user replaceable) |
Memory size | Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events |
Basic Interval | |
Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy |
Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms) |
Demand Interval (Energy Meter Mode) | |
Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy |
Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off |
Power Quality Measurements | |
Measured parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage inter-harmonics, TID V, current inter-harmonics, TID A, Flicker, Mains Signaling, under/over deviation |
Averaging interval | 10 min for all parameters 2 hrs (long term Flicker PLT) 150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT) |
Individual harmonics | 2nd to 50th harmonic Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + inter-harmonics), grouped or harmonic bins only |
Inter-harmonics | 1st to the 50th inter-harmonic |
Total harmonic distortion | Calculated on 50 voltage harmonics |
Events | Voltage: dips, swells, interruptions, current: inrush current 1748: mains signaling, transients (low frequency) |
Triggered recordings | RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30) |
Waveform of voltage and current up to 200 ms, 10/12 cycles | |
Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s | |
Inrush | RMS profile based on 1/2 cycle RMS steady state triggering |
Flicker | In accordance with IEC 61000-4-15 and IEEE 1453 |
Mains signaling | Two user defined frequencies up to 3 kHz |
PQ Health | Summarizes power quality measurements in one table. Detailed data available for each parameter |
EN 50160 | Compliance with standard |
Programmable PQ limits | Enables user defined limits for local standards compliance |
General Specifications | |
Warranty | Two-years (battery not included) |
Accessories: one-year | |
Calibration cycle: two-years | |
Dimensions | 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in) |
Weight | Instrument: 1 kg (2.2 lb) |
Tamper protection | Accept securing cables (max. Φ 6mm) |
1Warm up the product to -10 °C (+14 °F) before you power the unit on | |
i17XX-FLEX1.5KIP Flexible Current Probe Specifications | |
Measuring range | 1 to 150 A ac/10 to 1500 A ac |
Probe cable length | 610 mm (24 in) |
Probe cable diameter | 7.5 mm (0.3 in) |
Weight | 170 g (0.38 lb) |
Minimum bending radius | 38 mm (1.5 in) |
Nondestructive current | 100 kA (50/60 Hz) |
Temperature coefficient over operating temperature range | 0.05 % of reading/°C (0.028 % of reading/°F) |
Working voltage | 1000 V CAT III, 600 V CAT IV |
Output cable length | 2.0 m (6.5 ft) |
Probe cable material | TPR |
Weight | 115 g |
Probe cable material | TPR |
Coupling material | POM + ABS/PC |
Output cable | TPR/PVC |
Operating temperature | -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F) |
Temperature, non-operating | -40 °C to +80 °C (-40 °F to 176 °F) |
Relative humidity, operating | 15% to 85% non-condensing |
IP rating | IEC 60529: IP65 |
Warranty | One-year |