• Store Locator
  • Schedule a
    Demo
  • Add products to your Toolbox to save it for requesting a quote while you keep browsing for other products to complete your list.

    My
    Toolbox
  • expression
    Create a Requisition

    FLUKE 1623-2 Kit Basic GEO Earth Ground Tester Kit

    # 1623-2 Kit

    • 3 and 4-pole fall of potential earth resistance loop testing
    • Comes with earth tester; USB cable; 2 clamps; carrying case; earth ground stakes and cable reels
    • 4-wire; 3-wire and stakeless testing
    FLUKE
    • FLUKE
    • 1623-2 Kit
    • Type

    Quantity:

    - +
      ADD TO MY TOOLBOX
    Where to buy this product?

    Stakeless Testing

     

    The Fluke 1623-2 earth ground tester is able to measure earth ground loop resistances using only clamps. With this test method, two clamps are placed around the earth ground rod and each are connected to the tester. No earth ground stakes are used at all. A known, fixed voltage is induced by one clamp and the current is measured using the second clamp. Then the tester automatically determines the resistance of the earth ground rod. This test method only works if a bonded earth ground system exists for the building or structure under test, but most are. If there is only one path to ground, like at many residential applications, the Stakeless method will not provide an acceptable value and the Fall-of-Potential test method must be used.

    With Stakeless testing, the earth ground rod does not need to be disconnected – leaving the bonded earth ground system intact during test. Gone are the days of spending time placing and connecting stakes for each earth ground rod on your system – a major time saver. You can also perform earth ground tests in places you’ve not considered before: inside buildings, power pylons, or anywhere you don’t have access to soil.

     

    The Most Complete Tester

     

    The Fluke 1623-2 is a unique earth ground tester that can perform all four types of earth ground measurement.

    • 3- and 4-Pole Fall-of-Potential (using stakes)
    • 4-Pole Soil Resistivity Testing (using stakes)
    • Selective Testing (using 1 clamp and stakes)
    • Stakeless Testing (using 2 clamps only)
    • IP56 rated for outdoor use
    • Rugged carrying case
    • USB data storage and transfer
    General Specifications
    Display: 1999 digit LCD Display with special symbols, digit height 25 mm, fluorescent backlight
    User interface Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
    Robust, water and dust resistant Instrument is designed for tough environmental conditions (rubber protective cover, IP56)
    Memory Internal memory storage up to 1500 records accessible via USB port
    Temperature Range
    Operating temperature -10°C to 50°C (14°F to 122°F)
    Storage temperature -30°C to 60°C (-22°F to 140°F)
    Temperature coefficient ±0.1% of reading/°C < 18°C > 28°C
    Intrinsic error Refers to the reference temperature range and is guaranteed for 1 year
    Operating error Refers to the operating temperature range and is guaranteed for 1 year
    Climatic class C1 (IEC 654-1), -5°C to +45°C (23° to +115° F), 5% to 95% RH
    Protective type IP56 for case, IP40 for battery door according to EN60529
    Safety Protection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: Pollution degree 2
    EMC (emission immunity) IEC61326-1: Portable
    Quality system Developed, designed and manufactured according to DIN ISO 9001
    External voltage V ext, max = 24 V (DC, AC < 400 Hz), measurement inhibited for higher values
    V ext rejection > 120 dB (162⁄3, 50, 60, 400 Hz)
    Measuring time Typical 6 seconds
    Max. overload 250 V rms (pertains to misuse)
    Auxiliary power 6 x 1.5 V Alkaline (type AA LR6)
    Battery life span Typical > 3,000 measurements
    Dimensions (W x H x D) 250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in)
    Weight 1.1 kg (2.43 lb) including batteries
    7.6 kg (16.8 lb) incl. accessories and batteries in carrying case
    RA 3-Pole Ground Resistance Measurement (IEC 1557-5)
    Switch position RA 3-pole
    Resolution 0.001 Ω to 10 Ω
    Measuring range 0.020 Ω to 19.99 kΩ
    Accuracy ±(2% rdg + 3 d)
    Operating error ±(5% rdg + 3 d)
    Measuring Principle: Current/Voltage Measurement
    Measuring voltage Vm = 48 V AC
    Short-circuit current > 50 mA
    Measure frequency 128 Hz
    Probe resistance (RS) Max 100 kΩ
    Auxiliary earth electrode resistance (RH) Max 100 kΩ
    Additional error from RH and RS RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
    Monitoring of RS and RH with error indicator.
    Automatic range selection.
    Measurement is not performed if the current through the current clamp is too low.
    RA 4-Pole Ground Resistance Measurement (IEC 1557-5)
    Switch position RA 4-pole
    Resolution 0.001 Ω to 10 Ω
    Measuring range 0.020 Ω to 19.99 kΩ
    Accuracy ±(2% rdg + 3 d)
    Operating error ±(5% rdg + 3 d)
    Measuring Principle: Current/Voltage Measurement
    Measuring voltage Vm = 48 V AC
    Short-circuit current > 50 mA
    Measure frequency 128 Hz
    Probe resistance (RS + RES) Max 100 kΩ
    Auxiliary earth electrode resistance (RH) Max 100 kΩ
    Additional error from RH and RS RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
    Monitoring of RS and RH with error indicator.
    Automatic range selection.
    RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )
    Switch position RA 3-pole with clamp
    Resolution 0.001 Ω to 10 Ω
    Measuring range 0.020 Ω to 19.99 kΩ
    Accuracy ±(7% rdg + 3 d)
    Operating error ±(10% rdg + 5 d)
    Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
    Measuring voltage Vm = 48 V AC
    Short-circuit current > 50 mA
    Measure frequency 128 Hz
    Probe resistance (RS) Max 100 kΩ
    Auxiliary earth electrode resistance (RH) Max 100 kΩ
    Monitoring of RS and RH with error indicator.
    Automatic range selection.
    Measurement is not performed if the current through the current clamp is too low.
    RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )
    Switch position RA 4-pole with clamp
    Resolution 0.001 Ω to 10 Ω
    Measuring range 0.020 Ω to 19.99 kΩ
    Accuracy ±(7% rdg + 3 d)
    Operating error ±(10% rdg + 5 d)
    Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
    Measuring voltage Vm = 48 V AC
    Short-circuit current > 50 mA
    Measure frequency 128 Hz
    Probe resistance (RS) Max 100 kΩ
    Auxiliary earth electrode resistance (RH) Max 100 kΩ
    Monitoring of RS and RH with error indicator.
    Automatic range selection.
    Measurement is not performed if the current through the current clamp is too low.
    Stakeless Ground Loop Measurement (2 Clamps )
    Switch position RA 4-pole 2 clamps
    Resolution 0.001 Ω to 10 Ω
    Measuring range 0.020 Ω to 19.99 kΩ
    Accuracy ±(7% rdg + 3 d)
    Operating error ±(10% rdg + 5 d)
    Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers
    Measuring voltage Vm = 48 V AC
    Measure frequency 128 Hz
    Noise current (IEXT) Max. IEXT = 10 A (AC) (RA < 20 Ω)
    Max. IEXT = 2 A (AC) (RA > 20 Ω)
    Automatic range selection.
    The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified.
    • GEO Earth Ground Tester
    • Users Manual
    • Batteries
    • Quick Reference Guide
    • USB Cable
    • 2 Clamps
    • C1620 Professional Carrying Case
    • 4 Earth Ground Stakes
    • 3 Cable Reels

    Provide us your contact detailsone of our product experts will contact you to discuss your needs or schedule a demonstration at a time that suits