Add products to your Toolbox to save it for requesting a quote while you keep browsing for other products to complete your list.
# 368FC
The Fluke 368 FC true-rms leakage current clamp meter helps users detect, document, record and compare leakage current readings over time as a means of preventing unplanned downtime, and identifying intermittent GFCI and RCD trips, all without taking equipment off line.
The Fluke 368 FC has a large 40 mm diameter jaw for work with large conductors. The clamp’s jaw is fully shielded to accurately capture very small leakage signals, and to minimize external electromagnetic interference.
The 368 FC also offers wireless data connectivity via Fluke Connect. As part of Fluke Connect — the industry’s largest system of software and more than 40 wireless test tools — the 368 FC allows you to track changes in leakage current over time, helping to identify potential problems before they turn into major failures.
Electrical Specifications | ||
Measurement function | Alternating current | |
AC ampere range | 3 mA, 30 mA, 300 mA, 3 A, 30 A, 60 A | |
mA / A: manual selection | ||
3 mA / 30 mA / 300 mA: automatic selection | ||
3 A / 30 A / 60 A: automatic selection | ||
Range / Resolution | 3 mA¹ / 0.001 mA | |
30 mA / 0.01 mA | ||
300 mA / 0.1 mA | ||
3 A / 0.001 A | ||
30 A / 0.01 A | ||
60 A / 0.1 A | ||
Accuracy – filter activated (40 to 70 Hz), filter off (40 to 1 kHz)² | 3 mA – 30 A | 1% + 5 digits |
60 A | 2% + 5 digits | |
Frequency | 40 Hz to 1 kHz | |
Crest Factor | 3 | |
After calibration accuracy is valid for one year. Accuracy is expressed as ± (% of reading + digits). Reference conditions 23 ±5 °C and a maximum relative humidity of 80%. | ||
¹The minimum value is 10 μA rms. | ||
²Outside of the TC / °C 18 °C to 28 °C, 0.02 + 1 | ||
Physical | ||
Display (LCD) | Digital readout: 3300 count | |
Display refresh rate | 4 times / sec | |
Maximum conductor diameter | 40 mm | |
Dimensions | 234 x 101 x 46 mm | |
Weight | 500 g | |
Battery | 2 AA, IEC LR6, NEDA 15A, alkaline | |
Battery life | Expected battery life, without using backlight and spotlight, is more than 150 hours | |
Automatic shut-down | Meter automatically shuts down after 15 minutes of inactivity | |
Safety and Environmental Specifications | ||
General safety | IEC 61010-1: Pollution Degree 2 | |
Measurement safety | IEC 61010-2-032: CAT III 600 V / CAT IV 300 V | |
Operating temperature | -10 °C to +50 °C | |
Storage temperature | -40 °C to +60 °C | |
Operating humidity | Non-condensing (<10 °C) | |
90% relative humidity (10 °C to 30 °C) | ||
75% relative humidity (30 °C to 40 °C) | ||
45% relative humidity (40 °C to 50 °C) | ||
Protection class | IEC 60529: IP30 (jaw closed) | |
Operating altitude | 2000 m | |
Storage altitude | 12000 m | |
Current sensor action category | IEC 61557-13: Class 2, ≤30 A / m | |
Electromagnetic compatibility (EMC) | ||
International | ||
IEC 61326-1 | Industrial Electromagnetic Environment | |
CISPR 11 | Group 1 Class B | |
Group 1 | Generated inside the equipment and / or use radio frequency energy associated with conducting the energy for the device’s own internal functions is essential. | |
Class B | Equipment for home appliances and residential buildings directly connected to a low voltage power supply network equipment. When this device is connected to a test object, it may exceed the emission levels produced by CISPR 11 requirements. | |
Korea (KCC): A type of equipment (radio and communication equipment industry) | ||
Class A | This product meets the requirements of industrial electromagnetic equipment, vendors or users should be aware of this. This device is intended for use in a commercial environment, instead of the home environment. | |
USA (FCC): 47 CFR 15 B Subpart. In accordance with section 15.103 provides that the products are considered tax-free device. |
Product selected: Model #
*Demonstrations can only be scheduled within the UAE