  • FLUKE 1746-30-INTL Power Quality Logger w/60 cm 3,000A iFlex

    # 1746-30-INTL

    • Functions: Voltage, current, power, power factor, frequency; Energy forward/reverse; Peak Demand; THD; Voltage and current harmonics (to 50th); Flicker; Unbalance
    • Rapid voltage change events; Interharmonics (to 50th); Dips, swells, interruption and transient events tables; Mains signaling; Inrush current
    • Recording: Trend

    Troubleshoot, quantify energy usage and perform quality of service surveys easier than ever

    It provides you with fast and easy access to the data you need to make real-time decisions, about critical power quality and energy.

     

    Compact and rugged, this three-phase power quality logger is specifically for technicians and engineers who need the flexibility to troubleshoot, quantify energy usage and analyze power distribution systems. Fully compliant with international power quality standards such as IEC 61000-4-30 and capable of simultaneously logging up to 500 parameters while also capturing events, this unit helps uncover intermittent and hard-to-find power quality issues more easily than ever. It comes equipped with an Energy Analyze plus software which quickly assesses the quality of power at the service entrance, substation, or at the load, according to national and international standards like EN 50160 and IEEE 519.

     

    An optimized user interface, flexible current probes, and an intelligent measurement verification function that allows you to digitally verify and correct connections make setup easier than ever and reduce measurement uncertainty. Minimize your time in potentially hazardous environments and reduce the hassle of suiting up in PPE by using a wireless connection (WiFi) to view data directly in the field.

     

    Features

    • Measure all three voltage and current phases plus the neutral current
    • Comprehensive logging
    • Measure with premium accuracy
    • Capture dips, swells and interruptions
    • Measure key power quality parameters
    • Optimized user interface
    • Flexible power supply
    • Rugged and reliable
    • Two external USB ports
    • Ethernet connectivity
    • Compact size
    • Highest safety rating in the industry
    • Optimized measurement accessories
    • Battery life
    • Security

     

    Software Features

    • “In-workshop” or “in-the-field” setup and download through PC application software: simple download using USB memory stick, WiFi download, wired ethernet connection or via USB cable
    • Energy Analyze plus application software: download and analyze every measured detail of energy consumption and power quality state-of-health with automated reporting
    • One touch reporting: create standardized reports according to commonly used standards like EN 50160, IEEE 519, GOST 33073 or export data in PQDIF or NeQual compatible format for use with third party software
    • Advanced analysis: choose any available logged parameter to create a highly customized view of logged measurements for advanced correlation of data
    Accuracy
    VoltageRange: 1000 V
    Maximum resolution: 0.1 V
    Intrinsic accuracy at reference conditions (% of reading +% of range): ±0.1 % of nominal voltage
    i17xx-flex 3000IP 24 3000 ARange: 300, 3000 A
    Maximum resolution: 0.01 A (min. 3.0 A)3, 0.1 A
    Intrinsic accuracy at reference conditions (% of reading +% of range): ±(1% + 0.03%)
    VoltageRange: 42.5 to 69 Hz
    Maximum resolution: 0.01 Hz
    Intrinsic accuracy at reference conditions (% of reading +% of range): ±(0.1%)2
    Auxiliary InputRange: ±10 V DC
    Maximum resolution: 0.1 mV
    Intrinsic accuracy at reference conditions (% of reading +% of range): ±(0.2% + 0.02%)
    Voltage Min/MaxRange: 1000 V
    Maximum resolution: 0.1 V
    Intrinsic accuracy at reference conditions (% of reading +% of range): ±0.2 % of nominal input voltage
    Current Min/MaxRange: Defined by accessory
    Maximum resolution: Defined by accessory
    Intrinsic accuracy at reference conditions (% of reading +% of range): ±(5% + 0.2%)
    THD on VoltageRange: 1000%
    Maximum resolution: 0.10%
    Intrinsic accuracy at reference conditions (% of reading +% of range): ± 2.5%
    THD on CurrentRange: 1000%
    Maximum resolution: 0.10%
    Intrinsic accuracy at reference conditions (% of reading +% of range): ± 2.5%
    Voltage Harmonics 2nd to 50thRange: 1000 V
    Maximum resolution: 0.1 V
    Intrinsic accuracy at reference conditions (% of reading +% of range): ≥1 V: ±5% of reading, <1 V: ±0.05 V
    Current Harmonics 2nd to 50thRange: Defined by accessory
    Maximum resolution: Defined by accessory
    Intrinsic accuracy at reference conditions (% of reading +% of range): ≥3% of current range: ±5% of reading, <3% of current range: ±0.15% of range
    Flicker PLT, PSTRange: 0 to 20
    Maximum resolution: 0.01
    Intrinsic accuracy at reference conditions (% of reading +% of range): 5%
    Electrical Specifications
    Voltage Range100 to 500 V using safety plug input when powering from the measurement circuit
    100 to 240 V MA-C8 and using standard power cord (IEC 60320 C7)
    Power ConsumptionMaximum 50 VA (max. 15 VA when powered using MA-C8 adapter)
    Efficiency≥68.2% (in accordance with energy efficiency regulations)
    Maximum No-Load Consumption<0.3 W only when powered using IEC 60320 input
    Mains Power Frequency50/60 Hz ±15%
    BatteryLi-ion 3.7 V, 9.25 Wh, customer-replaceable
    On-Battery RuntimeTypically 4 hours
    Charging Time<6 hours
    Data Acquisition
    Resolution16-bit synchronous sampling
    Sampling Frequency10.24 kHz at 50/60 Hz, synchronized to mains frequency
    Input Signal Frequency50/60 Hz (42.5 to 69 Hz)
    Circuit Types1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies)
    Data StorageInternal flash memory (not user replaceable)
    Memory SizeTypical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events
    Basic Interval
    Measured ParametersVoltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
    Averaging IntervalUser selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
    Averaging Time Min/Max ValuesVoltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms)
    Demand Interval (Energy Meter Mode)
    Measured ParametersEnergy (Wh, varh, VAh), PF, maximum demand, cost of energy
    IntervalUser selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
    Power Quality Measurements
    Measured ParameterVoltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation
    Averaging Interval10 min for all parameters
    2 hrs (long term Flicker PLT)
    150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT)
    Individual Harmonics2nd to 50th harmonic
    Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only
    Interharmonics1st to the 50th interharmonic
    Total Harmonic DistortionCalculated on 50 voltage harmonics
    EventsVoltage: dips, swells, interruptions, current: inrush current
    Triggered RecordingsRMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30)
    Waveform of voltage and current up to 200 ms, 10/12 cycles
    Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120 s
    InrushRMS profile based on ½ cycle RMS steady state triggering
    FlickerIn accordance with IEC 61000-4-15 and IEEE 1453
    Mains SignalingTwo user defined frequencies up to 3 kHz
    PQ HealthSummarizes power quality measurements in one table. Detailed data available for each parameter
    EN 50160Compliance with standard
    Programmable PQ LimitsEnables user defined limits for local standards compliance
    Standards Compliance
    HarmonicsIEC 61000-4-7: Class 1
    IEEE 519 (short time and very short time harmonics)
    Power QualityIEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device)
    PowerIEEE 1459
    Power Quality ComplianceEN 50160
    SafetyGeneral: IEC 61010-1: Pollution Degree 2
    Measurement: IEC 61010-2-033: CAT IV 600 V/CAT III 1000 V
    Power Supply: Overvoltage Category IV, Pollution Degree 2
    Li-ion Battery: IEC 62133
    Interfaces
    USB-AFile transfer via USB flash drive, firmware updates, max. supply current: 120 mA
    Wi-FiFile transfer and remote control via direct connection or Wi-Fi infrastructure
    BluetoothRead auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or Wi-Fi/BLE adapter, check for availability)
    USB-MiniData download device to PC
    Voltage Inputs
    Number of Inputs4 (3 phases referenced to neutral)
    Maximum Input Voltage1000 Vrms, CF 1.7
    Input impedance10 MΩ
    Bandwidth42.5 Hz to 3.5 kHz
    Scaling1:1 and variable
    Measurement Category1000 V CAT III/600 V CAT IV
    Current Inputs
    Number of Inputs4 (3 phases and neutral), mode selected automatically for attached sensor
    Input VoltageClamp input: 500/50 mVrms; CF 2.8
    Rogowski coil input: 150/15 mVrms at 50 Hz, 180/18 mVrms at 60 Hz
    CF 4 all at nominal probe range
    Range1 to 150 A/10 to 1500 A with thin flexible current probe i17XX-flex1500 IP 24
    Bandwidth42.5 Hz to 3.5 kHz
    Scaling1:1 and variable
    Auxiliary Inputs
    Number of Inputs2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously)
    Input Range0 to ± 10 V DC, or 0 to ± 1000 V DC (with optional adapter), 1 reading/s
    Scale FactorFormat: mx + b (gain and offset) user configurable
    Displayed UnitsUser configurable (7 characters, for example, °C, psi, or m/s)
    Wireless Bluetooth Connection
    Number of Inputs2
    Supported ModulesFluke Connect® 3000 series
    Acquisition1 reading/s
    Environmental Specifications
    Operating Temperature-13 to 122°F (-25 to 50°C)
    Storage TemperatureWithout battery: -13 to 140°F (-25 to 60°C)
    With battery: −4 to 122°F (-20 to 50°C)
    Operating HumidityIEC 60721-3-3: 3K6:
    -13 to 86°F (-25 to 30°C): ≤100%
    104°F (40°C): 55%
    122°F (50°C): 35%
    Operating Altitude6561.7′ (2000 m) up to 13,123.4′ (4000 m) derate to 1000 V CAT II/600 V CAT III/300 V CAT IV
    Storage Altitude39,370.1′ (12,000 m)
    EnclosureIEC 60529: IP50
    IEC 60529: IP65 with IP65 rated voltage connector
    VibrationIEC 60721-3-3 /3M2
    Electromagnetic Compatibility (EMC)EN 61326-1: Industrial CISPR 11: Group 1, Class A
    IEC 61000-6-5 Power station environment
    Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
    USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
    General Specifications
    Dimensions9.1 x 7.1 x 2.1″ (23 x 18 x 5.4 cm)
    Weight2.2 lbs (1 kg)
    Tamper ProtectionAccept securing cables (max. Φ 6mm)
    • Logger
    • USB Stick
    • USB Cable
    • Neutral Voltage Test Lead
    • 7.1″ (0.18 m) Test Lead Set
    • 59″ (1.5 m) Test Lead Set
    • 4 x Current Probes
    • 4 x Aligator Clips
    • Cable Market Kit
    • Magnet Probe Set
    • Carrying Case

    Provide us your contact detailsone of our product experts will contact you to discuss your needs or schedule a demonstration at a time that suits

    Product selected: Model #







      *Demonstrations can only be scheduled within the UAE

      Sign up to stay in the know-how of our latest products, updates, special offers, and more.

      • Subscription Form