# 6500-2 Uk
Test Specifications | The accuracy specification for the display range is defined as ±(%reading + digit counts) at 23 °C ±5 °C, ≤75 % RH. | |
Between 0 °C and 18 °C and between 28 °C and 40 °C, accuracy specifications may degrade by 0.1 x (accuracy specification) per °C. | ||
The measurement range meets the service operating errors specified in EN61557-1: 1997, EN61557-2: 1997, EN61557-4: 1997, EN61557-6: 1997, DIN VDE0404-2. | ||
Power-on Test | The test indicates reversed L-N, missing PE, and measures the mains voltage and frequency. | |
Display Range | 90 V to 264 V | |
Accuracy at 50 Hz | ± (2% + 3 counts) | |
Resolution | 0.1 V | |
Input Impedance | > 1 MΩ // 2.2 nF | |
Maximum Input Mains Voltage | 264 V | |
Earth Bond Test (Rpe) | Display Range | 0 to 19.99 Ω |
Accuracy (After Bond Test Zeroing) | ± (2.5% + 4 counts) | |
Resolution | 0.01 Ω | |
Test Current | 200 mA AC -0% +40% into 1.99 Ω 25 A AC ± 20% into 25 mΩ at 230 V | |
Open Circuit Voltage | > 4 V AC, < 24 V AC | |
Bond Test Zeroing | can subtract up to 1.99 Ω | |
Insulation Test (Riso) | Display Range | 0 to 299 MΩ |
Accuracy | ± (5% + 2 counts) from 0.1 to 300 MΩ | |
Resolution | 0.01 MΩ (0 to 19.99 MΩ) 0.1 MΩ (20 to 199.9 MΩ) 1 MΩ (200 to 299 MΩ) | |
Test Voltage | 500 V DC -0% + 25% at 500 kΩ load or 250 V dc -0 % +25 % at 250 kΩ load | |
Test Current | > 1 mA at 500 kΩ load, < 15 mA at 0 Ω | |
Auto Discharge Time | < 0.5 s for 1 μF | |
Max. Capacitive Load | Operational up to 1 μF | |
Touch Current Test | Display Range | 0 to 1.99 mA AC |
Accuracy | ± (4% + 2 counts) | |
Resolution | 0.01 mA | |
Internal Resistance (via Probe) | 2 kΩ | |
Measuring Method | Probe* | |
Substitute Leakage Current Test | Display Range | 0 to 19.99 mA AC |
Accuracy | ± (2.5% + 3 counts) | |
Resolution | 0.01 mA | |
Test Voltage | 100 V AC ± 20% | |
Load/Leakage Test: Load Current | Display Range | 0 A to 13 A |
Accuracy | ± (4% + 2 counts) | |
Resolution | 0.1 A* | |
Load/Leakage Test: Load Power | Display Range 230 V Mains | 0.0 VA to 3.2 kVA |
Accuracy | ± (5 % + 3 counts) | |
Resolution | 1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)* | |
Load/Leakage Test: Leakage Current | Display Range | 0 to 19.99 mA |
Accuracy | ± (4% + 4 counts) | |
Resolution | 0.01 mA* | |
PELV Test | Accuracy at 50 Hz | ± (2% + 3 counts) |
Overload Protection | 300 V rms | |
Warning Threshold | 25 V rms | |
RCD Test: Trip Current | Operational Error | ±10 % |
Nominal | 30 mA | |
Accuracy | ±5 % | |
RCD Test: Trip Time | Standard Requirement | 61557 Part 6; tolerance of rated test current 0 % to +10 % |
Operational Error | ±10 % | |
RCD Type | AC general-purpose 30 mA | |
Display Range | 310 ms | |
Resolution | 0.1 ms | |
Accuracy | 3 ms | |
Trip Time Limit at 100 % (30 mA) | 300 ms | |
Trip Time Limit at 500 % (150 mA) | 40 ms | |
*The appliance under test is energized at mains potential. |