  • FLUKE 1736-INTL 3Phase Power Logger; Network Analyzer

    # 1736-INTL

    • 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream
    • Key power measurements-All measurements are measured and logged to eliminate the risk of not recording the important parameters
    • Automatically captures and logs voltage, current, power, harmonics and associated power quality values.

    Ready to see it in action? Please provide us with your contact information, and one of our technical experts will contact you to schedule your product demonstration.

    • Versatile, three-phase Fluke Connect-compatible power logger for conducting basic energy and power quality studies
    • Automatically captures and logs voltage, current, power, harmonics and associated power quality values.
    • Provides the highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream
    • Automatically logs all measured values and stores more than 20 separate logging sessions
    Specifications
    Accuracy
    ParameterRangeResolutionIntrinsic Accuracy at Reference Conditions (% of Reading +% of Full Scale)
    Voltage1000 V0.1 V±(0.2% + 0.01%)
    Current: Direct inputi17xx-flex 1500 12″150 A0.1 A±(1% + 0.02%)
    1500 A1:00 AM±(1% + 0.02%)
    i17xx-flex 3000 24″300 A1:00 AM±(1% + 0.03%)
    3000 A10:00 AM±(1% + 0.03%)
    i17xx-flex 6000 36″600 A1:00 AM±(1.5% + 0.03%)
    6000 A10:00 AM±(1.5% + 0.03%)
    i40s-EL clamp4:00 AM1 mA±(0.7% + 0.02%)
    40 A10 mA±(0.7% + 0.02%)
    Frequency42.5 Hz to 69 Hz0.01 Hz±(0.1%)
    Auxillary input±10 V dc0.1 mV±(0.2% + 0.02%)
    Voltage min/max1000 V0.1 V±(1% + 0.1%)
    Current min/maxDefined by accessoryDefined by accessory±(5% + 0.2%)
    THD on voltage1000%0.10%±0.5
    THD on current1000%0.10%±0.5
    Voltage harmonics 2nd to 50th1000 V0.1 V≥ 10 V: ±5% of reading
    < 10 V: ±0.5V
    Current harmonics 2nd to 50thDefined by accessoryDefined by accessory≥ 3% of current range: ±5% of reading
    < 3% of current range: ±0.15% of range
    Unbalance100%0.10%±0.2
    Intrinsic Uncertainty ±(% of reading +% of range)¹
    ParameterInfluence quantityiFlex1500-12iFlex3000-24iFlex6000-36i40S-EL
    150 A / 1500 A300 A / 3000 A600 A / 6000 A4 A / 40 A
    Active Power PPF ≥ 0.991.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
    Active Energy EaPF ≥ 0.991.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
    Apparent power S0 ≤ PF ≤ 11.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
    Apparent Energy Eap0 ≤ PF ≤ 11.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
    Reactive power Q0 ≤ PF ≤ 12.5% of measured apparent power
    Reactive Energy Er0 ≤ PF ≤ 12.5% of measured apparent power
    Power Factor PF±0.025
    Displacement Power Factor±0.025
    DBF/cosϕ±0.025
    Additional uncertainty in% of range¹VP-N>250 V0.02%0.02%0.02%0.02%
    ¹Range = 1000 V x I range
    Reference conditions:
    Environmental: 23 °C ±5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65%
    Input conditions: Cosϕ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10%.
    Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V Input current: I > 10% of I range
    Primary conductor of clamps or Rogowski coil in center position
    Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
    Electrical Specifications
    Power Supply
    Voltage range100 V to 500 V using safety plug input when powering from the measurement circuit
    100 V to 240 V using standard power cord (IEC 60320 C7)
    Power consumptionMaximum 50 VA (max. 15 VA when powered using IEC 60320 input)
    Efficiency≥ 68.2% (in accordance with energy efficiency regulations)
    Maximum no-load consumption< 0.3 W only when powered using IEC 60320 input
    Mains power frequency50/60 Hz ±15%
    BatteryLi-ion 3.7 V, 9.25 Wh, customer-replaceable
    On-battery runtimeFour hours in standard operating mode, up to 5.5 hours in power saving mode
    Charging time< 6 hours
    Data Acquisition
    Resolution16-bit synchronous sampling
    Sampling frequency10.24 kHz at 50/60 Hz, synchronized to mains frequency
    Input signal frequency50/60 Hz (42.5 to 69 Hz)
    Circuit types1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies)
    Data storageInternal flash memory (not user replaceable)
    Memory sizeTypical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹
    ¹The number of possible logging sessions and logging period depends on user requirements.
    Basic Interval
    Measured parametersVoltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
    Averaging intervalUser selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
    Averaging time min/max valuesVoltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms
    Demand Interval (Energy Meter Mode)
    Measured parametersEnergy (Wh, varh, VAh), PF, maximum demand, cost of energy
    IntervalUser selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
    Power Quality Measurements
    Measured parameterVoltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD
    Averaging interval10 min
    Individual harmonics2nd to 50th harmonic
    Total harmonic distortionCalculated on 50 harmonics
    EventsVoltage: dips, swells, interruptions, current: inrush current
    Triggered recordingsFull cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30)
    Waveform of voltage and current
    Standards Compliance
    HarmonicsIEC 61000-4-7: Class 1
    IEEE 519 (short time harmonics)
    Power qualityIEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
    PowerIEEE 1459
    Power quality complianceEN50160 (for measured parameters)
    Interfaces
    USB-AFile transfer via USB flash drive, firmware updates
    Max. current: 120 mA
    WiFiFile transfer and remote control via direct connection or WiFi infrastructure
    BluetoothRead auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option)
    USB-miniData download device to PC
    Voltage Inputs
    Number of inputs4 (3 phases and neutral)
    Maximum input voltage1000 Vrms, CF 1.7
    Input impedance10 MΩ
    Bandwidth (-3 dB)42.5 Hz – 3.5 kHz
    Scaling1:1 and variable
    Measurement category1000 V CAT III/600 V CAT IV
    Current Inputs
    Number of inputs4, mode selected automatically for attached sensor
    Input voltageClamp input: 500 mVrms/50 mVrms; CF 2.8
    Rogowski coil input150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
    Range1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12″
    3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24″
    6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36″
    40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
    Bandwidth (-3 dB)42.5 Hz – 3.5 kHz
    Scaling1:1 and variable
    Auxiliary Inputs
    Number of inputs2
    Input range0 to ±10 V dc, 1reading/s
    Scale factor (available 2014)Format: mx + b (gain and offset) user configurable
    Displayed units (available 2014)User configurable (7 characters, for example, °C, psi, or m/s)
    Wireless Connection
    Number of inputs2
    Supported modulesFluke Connect® 3000 series
    Acquisition1 reading/s
    Environmental Specifications
    Operating temperature-10 °C to +50 °C (14 °F to 122 °F)
    Storage temperature-20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
    Operating humidity10 °C to 30 °C (50 °F to 86 °F) max. 95% RH
    30 °C to 40 °C (86 °F to 104 °F) max. 75% RH
    40 °C to 50 °C (104 °F to 122 °F) max. 45% RH
    Operating altitude2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
    Storage altitude12,000m
    EnclosureIP50 in accordance with EN60529
    VibrationMIL-T-28800E, Type 3, Class III, Style B
    SafetyIEC 61010-1
    IEC Mains Input: Overvoltage Category II, Pollution Degree 2
    Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
    IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
    Electromagnetic compatibilityEN 61326-1: Industrial CISPR 11: Group 1, Class A
    Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
    USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
    Temperature coefficient0.1 x accuracy specification/°C
    General Specifications
    Color LCD display4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
    WarrantyInstrument and power supply: Two-years (battery not included)
    Accessories: one-year
    Calibration cycle: two-years
    DimensionsInstrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
    Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
    Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in)
    WeightInstrument: 1.1 kg (2.5 lb)
    Power supply: 400 g (0.9 lb)
    Tamper protectionKensington lock slot
    i17xx-flex 1500 12″ Flexible Current Probe Specifications
    Measuring range1 to 150 A ac/10 to 1500 A ac
    Nondestructive current100 kA (50/60 Hz)
    Intrinsic error at reference condition*±0.7% of reading
    Accuracy 173x + iFlex±(1% of reading + 0.02% of range)
    Temperature coefficient over operating temperature range0.05% of reading/°C 0.09% of reading/°F
    Working voltage1000 V CAT III, 600 V CAT IV
    Probe cable length305 mm (12 in)
    Probe cable diameter7.5 mm (0.3 in)
    Minimum bending radius38 mm (1.5 in)
    Output cable length2 m (6.6 ft)
    Weight115 g
    Probe cable materialTPR
    Coupling materialPOM + ABS/PC
    Output cableTPR/PVC
    Operating temperature-20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
    Temperature, non-operating-40 °C to +80 °C (-40 °F to 176 °F)
    Relative humidity, operating15% to 85% non-condensing
    IP ratingIEC 60529:IP50
    WarrantyOne-year
    * Reference condition:
    Environmental: 23 °C ±5 °C, no external electrical/magnetic field, RH 65%
    Primary conductor in center position
    • 1 – WiFi Adapter
    • 1 – 4GB USB Flash Drive
    • 1 – USB Cable
    • 1 – Flat Cable (3PHVL-173)
    • 1 – .1m Cable (Red)
    • 1 – .1m Cable (Black)
    • 1 – 1.5m Test Lead (Red)
    • 1 – 1.5m Test Lead (Black)
    • 4 – Alligator Clips
    • 1 – Soft Carrying Case (C173X)
    • 1 – Color Coding Set
    • 4 – 12 in. Flexible Probes (i173X-FLEX1500)
    • 1 – EU/US/UK Line Cord
    • 1 – Energy Analyze Plus Software (Thumb Drive)