• Store Locator
  • Schedule a
    Demo
  • Add products to your Toolbox to save it for requesting a quote while you keep browsing for other products to complete your list.

    My
    Toolbox
  • FLUKE 1734-INTL 3Phase Electrical Energy Logger / Wireless

    # 1734-INTL

    • Trace the energy utilization profile at your facility
    • Help identify energy-saving opportunities
    • Get the data you need to act accordingly.
    • Key measurements: Automatically capture and log voltage, current, power, power factor, energy and associated values
    • Fluke Connect® compatible: View data locally on the instrument, via Fluke Connect mobile app and desktop software or through your facilities’ WiFi infrastructure
    • Convenient instrument powering: Power instrument directly from the measured circuit
    • Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream
    • Measure all three phases: With included 3 flexible current probes
    • Comprehensive logging: More than 20 separate logging sessions can be stored on the instruments. In fact, all measured values are automatically logged so you never loose measurement trends. They can even be reviewed during logging sessions and before downloading for real-time analysis
    • Optimized user interface: Quick, guided, graphical setup ensures you’re capturing the right data every time, and the intelligent verification function indicates correct connections have been made, reducing user uncertainty
    • Bright, color touch screen: Perform convenient in-the-field analysis and data checks with full graphical display
    • Optimized user interface: Capture the right data every time with quick, guided, graphical setup and reduce uncertainty about your connections with the intelligent verification function
    • Complete “in-the-field” setup through the front panel or Fluke Connect: No need to return to the workshop for download and setup or to take a computer to the electrical panel
    • Energy Analyze Plus application software: Download and analyze every detail of energy consumption with our automated reporting
    Specifications
    Accuracy
    ParameterRangeResolutionIntrinsic Accuracy at Reference Conditions (% of Reading +% of Full Scale)
    Voltage1000 V0.1 V±(0.2% + 0.01%)
    Current: Direct inputi17xx-flex 1500 12″150 A0.1 A±(1% + 0.02%)
    1500 A1 A±(1% + 0.02%)
    i17xx-flex 3000 24″300 A1 A±(1% + 0.03%)
    3000 A10 A±(1% + 0.03%)
    i17xx-flex 6000 36″600 A1 A±(1.5% + 0.03%)
    6000 A10 A±(1.5% + 0.03%)
    i40s-EL clamp4 A1 mA±(0.7% + 0.02%)
    40 A10 mA±(0.7% + 0.02%)
    Frequency42.5 Hz to 69 Hz0.01 Hz±(0.1%)
    Auxillary input±10 V dc0.1 mV±(0.2% + 0.02%)
    Voltage min/max1000 V0.1 V±(1% + 0.1%)
    Current min/maxDefined by accessoryDefined by accessory±(5% + 0.2%)
    THD on voltage1000%0.1%±0.5
    THD on current1000%0.1%±0.5
    Intrinsic Uncertainty ±(% of reading +% of range)¹
    ParameterInfluence quantityiFlex1500-12iFlex3000-24iFlex6000-36i40S-EL
    150 A / 1500 A300 A / 3000 A600 A / 6000 A4 A / 40 A
    Active Power PPF ≥ 0.991.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
    Active Energy EaPF ≥ 0.991.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
    Apparent power S0 ≤ PF ≤ 11.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
    Apparent Energy Eap0 ≤ PF ≤ 11.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
    Reactive power Q0 ≤ PF ≤ 12.5% of measured apparent power
    Reactive Energy Er0 ≤ PF ≤ 12.5% of measured apparent power
    Power Factor PF±0.025
    Displacement Power Factor±0.025
    DBF/cosϕ±0.025
    Additional uncertainty in% of range¹VP-N>250 V0.015%0.0225%0.0225%0.015%
    ¹Range = 1000 V x Irange
    Reference conditions:

    • Environmental: 23 °C ±5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65%
    • Input conditions: Cosϕ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10%.
    • Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V Input current: I > 10% of Irange
    • Primary conductor of clamps or Rogowski coil in center position
    • Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
    Electrical Specifications
    Power Supply
    Voltage range100 V to 500 V using safety plug input when powering from the measurement circuit
    100 V to 240 V using standard power cord (IEC 60320 C7)
    Power consumptionMaximum 50 VA (max. 15 VA when powered using IEC 60320 input)
    Efficiency≥ 68.2% (in accordance with energy efficiency regulations)
    Maximum no-load consumption< 0.3 W only when powered using IEC 60320 input
    Mains power frequency50/60 Hz ±15%
    BatteryLi-ion 3.7 V, 9.25 Wh, customer-replaceable
    On-battery runtimeFour hours in standard operating mode, up to 5.5 hours in power saving mode
    Charging time< 6 hours
    Data Acquisition
    Resolution16-bit synchronous sampling
    Sampling frequency10.24 kHz at 50/60 Hz, synchronized to mains frequency
    Input signal frequency50/60 Hz (42.5 to 69 Hz)
    Circuit types1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies)
    Data storageInternal flash memory (not user replaceable)
    Memory sizeTypical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹
    ¹The number of possible logging sessions and logging period depends on user requirements.
    Basic Interval
    Measured parametersVoltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
    Averaging intervalUser selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
    Averaging time min/max valuesVoltage, Current: Full cycle RMS updated every half cycle Aux, Power: 200ms
    Demand Interval (Energy Meter Mode)
    Measured parametersEnergy (Wh, varh, VAh), PF, maximum demand, cost of energy
    IntervalUser selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
    Standards Compliance
    PowerIEEE 1459
    Interfaces
    USB-AFile transfer via USB flash drive, firmware updates
    Max. current: 120 mA
    WiFiFile transfer and remote control via direct connection or WiFi infrastructure
    BluetoothRead auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1734, or 1732 upgrade option)
    USB-miniData download device to PC
    Voltage Inputs
    Number of inputs4 (3 phases and neutral)
    Maximum input voltage1000 Vrms, CF 1.7
    Input impedance10 MΩ
    Bandwidth (-3 dB)42.5 Hz – 3.5 kHz
    Scaling1:1 and variable
    Measurement category1000 V CAT III/600 V CAT IV
    Current Inputs
    Number of inputs3, mode selected automatically for attached sensor
    Input voltageClamp input: 500 mVrms/50 mVrms; CF 2.8
    Rogowski coil input150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
    Range1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12″
    3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24″
    6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36″
    40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
    Bandwidth (-3 dB)42.5 Hz – 3.5 kHz
    Scaling1:1 and variable
    Auxiliary Inputs
    Number of inputs2
    Input range0 to ±10 V dc, 1reading/s
    Scale factor (available 2014)Format: mx + b (gain and offset) user configurable
    Displayed units (available 2014)User configurable (7 characters, for example, °C, psi, or m/s)
    Wireless Connection
    Number of inputs2
    Supported modulesFluke Connect® 3000 series
    Acquisition1 reading/s
    Environmental Specifications
    Operating temperature-10 °C to +50 °C (14 °F to 122 °F)
    Storage temperature-20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
    Operating humidity10 °C to 30 °C (50 °F to 86 °F) max. 95% RH
    30 °C to 40 °C (86 °F to 104 °F) max. 75% RH
    40 °C to 50 °C (104 °F to 122 °F) max. 45% RH
    Operating altitude2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
    Storage altitude12,000m
    EnclosureIP50 in accordance with EN60529
    VibrationMIL-T-28800E, Type 3, Class III, Style B
    SafetyIEC 61010-1
    IEC Mains Input: Overvoltage Category II, Pollution Degree 2
    Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
    IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
    Electromagnetic compatibilityEN 61326-1: Industrial CISPR 11: Group 1, Class A
    Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
    USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
    Temperature coefficient0.1 x accuracy specification/°C
    General Specifications
    Color LCD display4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
    WarrantyInstrument and power supply: Two-years (battery not included)
    Accessories: one-year
    Calibration cycle: two-years
    DimensionsInstrument: 19.8 x 16.7 x 5.5 cm (7.8 x 6.6 x 2.2 in)
    Power supply: 13.0 x 13.0 x 4.5 cm (5.1 x 5.1 x 1.8 in)
    Instrument with power supply attached: 19.8 x 16.7 x 9 cm (7.8 x 6.6 x 3.5 in)
    WeightInstrument: 1.1 kg (2.5 lb)
    Power supply: 400 g (0.9 lb)
    Tamper protectionKensington lock slot
    i17xx-flex 1500 12″ Flexible Current Probe Specifications
    Measuring range1 to 150 A ac/10 to 1500 A ac
    Nondestructive current100 kA (50/60 Hz)
    Intrinsic error at reference condition*±0.7% of reading
    Accuracy 173x + iFlex±(1% of reading + 0.02% of range)
    Temperature coefficient over operating temperature range0.05% of reading/°C 0.09% of reading/°F
    Working voltage1000 V CAT III, 600 V CAT IV
    Probe cable length305 mm (12 in)
    Probe cable diameter7.5 mm (0.3 in)
    Minimum bending radius38 mm (1.5 in)
    Output cable length2 m (6.6 ft)
    Weight115 g
    Probe cable materialTPR
    Coupling materialPOM + ABS/PC
    Output cableTPR/PVC
    Operating temperature-20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
    Temperature, non-operating-40 °C to +80 °C (-40 °F to 176 °F)
    Relative humidity, operating15% to 85% non-condensing
    IP ratingIEC 60529:IP50
    WarrantyOne-year
    * Reference condition:

    • Environmental: 23 °C ±5 °C, no external electrical/magnetic field, RH 65%
    • Primary conductor in center position
    • Energy Logger, International wireless version (includes current probes)
    • Power supply
    • Voltage test leads
    • Alligator clips (4x)
    • 12 in 1,500A flexible current probe (3x)
    • Soft case
    • Energy Analyze Plus software
    • Magnetic hanging strap
    • Magnetic voltage probes (4x)
    • WiFi/BLE adapter
    • Line cords
    • Color coding set
    • Documentation on USB flash drive

    Provide us your contact detailsone of our product experts will contact you to discuss your needs or schedule a demonstration at a time that suits

    Product selected: Model #







      *Demonstrations can only be scheduled within the UAE

      Sign up to stay in the know-how of our latest products, updates, special offers, and more.

      • Subscription Form