    FLUKE 1587MDT Advanced Motor & Drive Troubleshooting Kit

    # 1587MDT

    • Best Insulation tester and true RMS digital multimeter in one comprehensive tool
    • Ideal for use on everything from motors to generators; cables and switchgear
    • Insulation test voltages of 50V; 100V; 250V; 500V and 1000V
    • With the Fluke 1587; perform insulation tests; plus a wide-range of DMM tasks with confidence and ease.
    • Use the Fluke i400 with your Fluke 1587 to accurately measure AC current without breaking the circuit.
    • Check the rotation of three-phase motors easily and safely with the Fluke 9040.
    AC Voltage Measurements
    Range600 mV
    6 V
    60 V
    600 V
    1000 V
    Resolution0.1 mV
    0.001 V
    0.01 V
    0.1 V
    1 V
    50 to 60 Hz ±(% of Rdg + counts)±(1% + 3)
    ±(1% + 3)
    ±(1% + 3)
    ±(1% + 3)
    ±(2% + 3)
    60 to 5000 Hz ±(% of Rdg + counts)±(2% + 3)
    ±(2% + 3)
    ±(2% + 3)
    ±(2% + 3)1
    ±(2% + 3)1
    Low-Pass Filter Voltage
    Range600 mV
    6 V
    60 V
    600 V
    1000 V
    Resolution0.1 mV
    0.001 V
    0.01 V
    0.1 V
    1 V
    50 to 60 Hz ±(% of Rdg + counts)±(1% + 3)
    ±(1% + 3)
    ±(1% + 3)
    ±(1% + 3)
    ±(2% + 3)
    60 to 400 Hz ±(% of Rdg + counts)±(2% + 3) – (6% – 3)
    ±(2% + 3) – (6% – 3)
    ±(2% + 3) – (6% – 3)
    ±(2% + 3) – (6% – 3)
    ±(2% + 3) – (6% – 3)
    DC Voltage Measurement
    Range6 V dc
    60 V dc
    600 V dc
    1000 V dc
    Resolution0.001 V
    0.01 V
    0.1 V
    1 V
    Accuracy ±(% of Rdg + Counts)±(0.09% + 2)
    ±(0.09% + 2)
    ±(0.09% + 2)
    ±(0.09% + 2)
    Input Impedance10 MΩ (nominal), <100 pF
    Nominal Mode Rejection Ratio>60 dB at 50 or 60 Hz
    Common Mode Rejection Ratio>120 dB at dc, 50 or 60 Hz (1 k unbalance)
    DC Millivolts Measurement
    Range600 mVdc
    Resolution0.1 mV
    Accuracy ±(% of Rdg + Counts)±(0.1 + 1)
    DC and AC Current Measurement
    Range400 mA
    Resolution0.1 mA
    Accuracy ±(% of Rdg+Counts)±(1.5% + 2)1
    Burden Voltage (Typical)2 mV/mA
    Range60 mA
    Resolution0.01 mA
    Accuracy ±(% of Rdg+Counts)±(1.5% + 2)1
    Burden Voltage (Typical)2 mV/mA
    DC
    Range400 mA
    Resolution0.1 mA
    Accuracy ±(% of Rdg+Counts)±(0.2% + 2)
    Burden Voltage (Typical)2 mV/mA
    Range60 mA
    Resolution0.01 mA
    Accuracy ±(% of Rdg+Counts)±(0.2% + 2)
    Burden Voltage (Typical)2 mV/mA
    Overload600 mA for 2 minutes maximum
    Fuse Protection for mA Input0.44 mA, 1000 V, IR 10 kA
    AC ConversionInputs are ac-coupled and calibrated to the rms value of sine wave input
    Ohms Measurement
    Range600 Ω
    6 kΩ
    60 kΩ
    600 kΩ
    6 MΩ
    50 MΩ
    Resolution0.1 Ω
    0.001 kΩ
    0.01 kΩ
    0.1 kΩ
    0.001 MΩ
    0.01 MΩ
    Accuracy +(% of Rdg+Counts)1±(0.9% + 2)
    ±(0.9% + 2)
    ±(0.9% + 2)
    ±(0.9% + 2)
    ±(0.9% + 2)
    ±(1.5% + 3)
    Overload Protection1000 rms or dc
    Open Circuit Test Voltage<8 V dc
    Short Circuit Current<1.1 mA
    Diode Test
    Diode Test IndicationDisplay voltage drop: 0.6 V at1.0 mA nominal test current
    Accuracy±(2% + 3)
    Continuity Test
    Continuity IndicationContinuous audible tone for testresistance below 25 Ω and off above 100 Ω
    Maximum reading: 1000 Ω
    Open Circuit Voltage<8.0 V
    Short Circuit Current1.0 mA typical
    Overload Protection1000 V rms
    Response Time>1 m sec
    Frequency Measurement
    Range99.99 Hz
    999.9 Hz
    9.999 kHz
    99.99 kHz
    Resolution0.01 Hz
    0.1 Hz
    0.001 kHz
    0.01 kHz
    Accuracy ±(% of Rdg+Counts)±(0.1% + 1)
    ±(0.1% + 1)
    ±(0.1% + 1)
    ±(0.1% + 1)
    Frequency Counter Sensitivity
    600.0 mV acV ac Sensitivity (RMS Sine Wave)1 5 Hz to 20 kHz: 100.0 mV
    V ac Sensitivity (RMS Sine Wave)1 20 to 100 kHz: 150.0 mV
    DC Trigger Levels¹ to 20 kHz2: NA
    6.0 VV ac Sensitivity (RMS Sine Wave)1 5 Hz to 20 kHz: 1.0 V
    V ac Sensitivity (RMS Sine Wave)1 20 to 100 kHz: 1.5 V
    DC Trigger Levels¹ to 20 kHz2: -400.0 mV and 2.5 V
    60.0 VV ac Sensitivity (RMS Sine Wave)1 5 Hz to 20 kHz: 10.0 V
    V ac Sensitivity (RMS Sine Wave)1 20 to 100 kHz: 36.0 V
    DC Trigger Levels¹ to 20 kHz2: 1.2 V and 4.0 V
    600.0 VV ac Sensitivity (RMS Sine Wave)1 5 Hz to 20 kHz: 100.0 V
    V ac Sensitivity (RMS Sine Wave)1 20 to 100 kHz: NA
    DC Trigger Levels¹ to 20 kHz2: 12.0 V and 40.0 V
    1000.0 VV ac Sensitivity (RMS Sine Wave)1 5 Hz to 20 kHz: 300.0 V
    V ac Sensitivity (RMS Sine Wave)1 20 to 100 kHz: NA
    DC Trigger Levels¹ to 20 kHz2: 12.0 V and 40.0 V
    Capacitance
    Range1000 nF
    10.00 µF
    100.0 µF
    9999 µF
    Resolution1 nF
    0.01 µF
    0.1 µF
    1 µF
    Accuracy ±(% of Rdg+Counts)±(1.2% + 2)
    ±(1.2% + 2)
    ±(1.2% ± 90 counts)
    ±(1.2% ± 90 counts)
    Temperature Measurement
    Range-40 to 998°F (-40 to 537°C)
    Resolution0.1°F (0.1°C)
    Accuracy ±(% of Rdg+Counts)1±(1% + 10 counts)
    ±(1% + 18 counts)
    Insulation Specifications
    Measurement Range0.01 MΩ to 2 GΩ
    Test Voltages50, 100, 250, 500, 1000 V
    Test Voltage Accuracy20%, 0%
    Short-Circuit Test Current1 mA nominal
    Auto DischargeDischarge time <0.5 second for C=1 µF or less
    Live Circuit DetectionInhibit test if terminal voltage >30 V prior to initialization of test
    Maximum Capacitive LoadOperable with up to 1 µF load
    Output Voltage
    50 V (0% to +20%)Display range: 0.01 to 6.00 MΩ
    Resolution: 0.01 MΩ
    Test current: 1 mA at 50 kΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(3% + 5 counts)
    Display range: 6.0 to 50.0 MΩ
    Resolution: 0.1 MΩ
    Test current: 1 mA at 50 kΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(3% + 5 counts)
    100 V (0% to +20%)Display range: 0.01 to 6.00 MΩ
    Resolution: 0.01 MΩ
    Test current: 1 mA at 100 kΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(3% + 5 counts)
    Display range: 6.0 to 60.0 MΩ
    Resolution: 0.1 MΩ
    Test current: 1 mA at 100 kΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(3% + 5 counts)
    Display range: 6.0 to 100.0 MΩ
    Resolution: 0.1 MΩ
    Test current: 1 mA at 100 kΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(3% + 5 counts)
    250 V (0% to +20%)Display range: 0.1 to 60.0 MΩ
    Resolution: 0.1 MΩ
    Test current: 1 mA at 250 kΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(1.5% + 5 counts)
    Display range: 60 to 250 MΩ
    Resolution: 1 MΩ
    Test current: 1 mA at 250 kΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(1.5% + 5 counts)
    500 V (0% to +20%)Display range: 0.1 to 60.0 MΩ
    Resolution: 0.1 MΩ
    Test current: 1 mA at 500 kΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(1.5% + 5 counts)
    Display range: 60 to 500 MΩ
    Resolution: 1 MΩ
    Test current: 1 mA at 250 kΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(1.5% + 5 counts)
    1000 V (0% to +20%)Display range: 0.1 to 60.0 MΩ
    Resolution: 0.1 MΩ
    Test current: 1 mA at 1 MΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(1.5% + 5 counts)
    Display range: 60 to 600 MΩ
    Resolution: 1 MΩ
    Test current: 1 mA at 1 MΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(1.5% + 5 counts)
    Display range: 0.6 to 2.0 GΩ
    Resolution: 100 MΩ
    Test current: 1 mA at 1 MΩ
    Resistance accuracy ±(% of Rdg + Counts): ±(10% + 3 counts)
    • Fluke 1587 Insulation Multimeter
    • Fluke i400 Current Clamp
    • Fluke 9040 Phase Rotation Indicator
    • Remote probe
    • Test leads
    • Alligator clips
    • K-type thermocouple
    • Hard case
    • User documentation

    Provide us your contact detailsone of our product experts will contact you to discuss your needs or schedule a demonstration at a time that suits

    Product selected: Model #







      *Demonstrations can only be scheduled within the UAE

      Sign up to stay in the know-how of our latest products, updates, special offers, and more.